Marka | Calectro |
Ürün | UG-3-A5-0 |
Tanım | hava kanalı duman anahtarı |
Sipariş kodu | IMP3429413 |
Ağırlık | 1.3 |
Gümrük tarife numarası | 85311030 |
Teknik özellik | 230 V AC The Uniguard smoke detector was developed and combined to detect smoke in ventilation ducts a smoke detector with an adapter system, with tube and casing specifically designed for optimal airflow were designed by the smoke detector. The Unifuard smoke detector has an integrated Alarm relay for controlling ventilation flaps, stopping fans and activating acoustic and optical alarms, etc. The integrated service alarm relay informs you about upcoming maintenance before false alarms occur. The smoke detector has an intelligent control and monitoring circuit. This circuit adjusts sensitivity for optimal to allow the smoke detector to function over its entire service life. If the monitoring circuit can no longer compensate for contamination, a service alarm will occur issued. Uniguard Superflow has four pre-assembled cable entries with IP67 approval with automatic pull load anchoring for cable diameters of 4-11 mm, type Klikseal. The bayonet mount of the smoke detector makes it easier to install and remove. TECHNICAL DATA Power supply: 230 V AC ± 20% Max Power Consumption: 18mA Operating temperature ፦10°C to +55°C Maximum humidity: 99% RH Channel ventilation performance range: approx. 0.2 to 20 m/s approvals UG-3-A5O: VdS (Germany) detecter head: EN-54-7 Relay output: floating Smoke alarm relay: two 250 V, 5 A switching contacts Service alarm: one switching contact 250 V, 5 A Degree of protection: IP54 |
Calectro - UG-3-A5-0 hava kanalı duman anahtarı ürününün fiyatını ve teslimat süresini öğrenmek için lütfen sorunuzu bize e-postayla gönderin. Diğer model numaraları için de size tavsiyelerde bulunabiliriz. Alman endüstriyel pazarında sizin için en iyi fiyatı ve teslimat süresini bulmaya çalışıyoruz.
Yalnızca yeni ve orijinal ürünler satıyoruz.